P211(212)(213)(214)(215)(216)(217): Preset Run Reference 1(2)(3)(4)(5) - Santerno DCREG2 Series User Manual

Table of Contents

Advertisement

15P0059B3
USER MANUAL
7.2.77
P211(212)(213)(214)(215)(216)(217): P
R
EFERENCE
P... PresetSpdx
***** %
SELECTION: Among the seven preset run references to be stored, the valid one results from the closing
of one or more digital inputs that have been properly configured.
If three digital inputs are set to 1:Preset Speed A, 2:Preset Speed B and 3:Preset Speed C, the preset run
reference is determined by the table below, where a blank square indicates the digital input opening state
(or the input that has not been set) and the black square indicates the closing state:
Selected run reference
Main Ref
PresetSpd1
PresetSpd2
PresetSpd3
PresetSpd4
PresetSpd5
PresetSpd6
PresetSpd7
Among the seven preset run references, if you want to select only the first three ones, you just need to set
two digital inputs as 1:Preset Speed A and 2:Preset Speed B. For one reference only, you just need to set
one input to 1:Preset Speed A (first input), 2:Preset Speed B (second input), 3:Preset Speed C (fourth
input).
160/200
1(2)(3)(4)(5)(6)(7
P211 (212)(213)(214)(215)(216)(217): Preset Run Reference
P
1(2)(3)(4)(5)(6)(7)
P
P211 (212)(213)(214)(215)(216)(217) - PresetSpd1(2)(3)(4)(5)(6)(7)
-100. ... 100. %
R
P211: 5.00 %
D
P212: 20.0 %
P213: 10.0 %
P214: 0.00 %
P215: -5.00 %
P216: -20.0 %
P217: -10.0 %
F
P211: Preset run reference PresetSpd1.
P212: Preset run reference PresetSpd2.
P213: Preset run reference PresetSpd3.
P214: Preset run reference PresetSpd4.
P215: Preset run reference PresetSpd5.
P216: Preset run reference PresetSpd6.
P217: Preset run reference PresetSpd7.
These references are speed / voltage references to be used instead of the Main
Ref reference. Their polarity may be reversed using the Reverse function. If a
digital input programmed for the 6:Slave function (see par. C130 ... C135) is
closed, or if par. C050 has been directly programmed for the 3:Iref=Vref
function, then the above-mentioned preset run references become current
references.
When a run preset reference is entered, the START digital input is to be
enabled.
PresetSpdC
RESET
PresetSpdB
DCREG2
DCREG4
R
UN
PresetSpdA