DCREG2
DCREG4
2.9
CURRENT LIMIT CONTROL OPTIONS
2.9.1
In the speed and current control, the current internal limitation remains always activated. It is
generally set as single-value adjusting through parameter P050 and parameter P051 (default values:
100%) and always represents a percentage of the armature current rated value indicated by parameter
C000 (default value: 100%).
So, whenever a double-value adjusting is required, it is necessary to set also parameter P052 and
parameter P053 (default values: 100%) by fixing the switching speed threshold with parameter P054
(default value: 100%).
If a hyperbolic adjusting is to be programmed, set parameter P055, parameter P056 and parameter
P057 (default values: 100%).
2.9.2
A current overlimit (i.e. a permanent increase of the current limit) is available in case of heavy
torque demands. The limit overcurrent value may be programmed through par. P060 and P061 (default
value: 100%). If the current required is inconsistent with the max. allowable duty-cycle (150% of the
nominal current for 1min every 10min), alarm A022 will trip (Drive It Trip).
2.9.3
On the other hand, to achieve a current limit decrease through an external command, it is
necessary to close one of the MDIx configurable digital inputs by programming parameters
C130(131)(132)(133)(134)(135) at value 4:Clim (said configuration is set by default on MDI5, terminal 36),
after setting the limit decrease value on parameter P058 (default value: 50%).
2.9.4
To enable or disable one or more work quadrants of the torque / speed plan, set parameter
C160 ... C163 (default values: 1
for DCREG4).
2.10 ANALOG AND DIGITAL OUTPUTS
2.10.1 The configurable analog outputs OUT1 and OUT2 are available on terminals 8 and 10. Their
meaning is indicated by parameters P150 and P153 respectively (default value: 0V). Any analog output
OUT1, OUT2 may include Gain operator (with parameter P152 and parameter P155 respectively; default
values: 100%), Bias operator (with parameter P151 and parameter P154 respectively; default values:
0%), and Polarity operator (with parameter P157 and parameter P158 respectively; default values:
Bipolar).
By moving jumpers JP409 and/or JP4010 from pos. 1-2 (standard) to pos. 2-3, said analog outputs turn to
0 ... 2 0mA current outputs respectively (outgoing current only: for the value to be set in the parameters
relating to Gain and Bias operators, see MILLIAMPERE INPUT / OUTPUT SIGNALS chapter).
2.10.2 The two non-configurable analog outputs have been already defined: n OUT on terminal 4 and
I OUT on terminal 6. The latter may be defined as polarity of the output signal through parameter P156
(default value: Bipolar for DCREG4, and Positive Only for DCREG2).
2.10.3 There are five MDOx configurable digital outputs. They are available on terminals 25-27, 29-
31, 33-35, 37-39 and 41-43, and are defined by parameters P170(176)(182)(188)(194). The MDOx
configurable digital outputs may include functions On Delay (with parameters P171(177)(183)(189)(195)
respectively and default values: 0s), Off Delay (with parameters P172(178)(184)(190)(196) respectively
and default values: 0s), Level (with parameters P173(179)(185)(191)(197) respectively and default
values: 50%, 3%, 50%, 5%, 50%), Hysteresis (with parameters P174(180)(186)(192)(198) respectively
and default values: 2%) and Logic (with parameters P175(181)(187)(193)(199) respectively and default
values: Normally Open).
st
and 2
quadrant enabled for DCREG2 and 1
nd
15P0059B3
USER MANUAL