7.2.75
P174(180)(186)(192)(198): D
S
W ITCHING
P... MDOxHyst
**
%
NOTE
NOTE
WARNING
7.2.76
P175(181)(187)(193)(199): D
C
ONTACT
P... MDOxLogic
***
H
YSTERESIS
P
P174(180)(186)(192)(198) - MDO1(2)(3)(4)(5)Hyst
0 ... 200 %
R
2 %
D
P174: Hysteresis level for the enabling/disabling of digital output 1 to term. 25
F
and 27.
P180: Hysteresis level for the enabling / disabling of digital output 2 to term. 29
and 31.
P186: Hysteresis level for the enabling / disabling of digital output 3 to term. 33
and 35.
P192: Hysteresis level for the enabling / disabling of digital output 4 to term. 37
and 39.
P198: Hysteresis level for the enabling / disabling of digital output 5 to term. 41
and 43.
This parameter defines the switching hysteresis of the digital output considered
below the value fixed by MDOxLevel. See also figure in the CONFIGURABLE
DIGITAL OPUTPUTS.
The hysteresis value set in these parameters may not exceed the level value set
in MDOxLevel-type parameters.
To avoid any drive malfunction, never save a value higher than the one saved
in EEPROM for MDOxLevel-type parameters.
L
OGIC
P
P175(181)(187)(193)(199) - MDO1(2)(3)(4)(5)Logic
0 ... 1
R
0
D
P175: It indicates the contact state when digital output 1 to term. 25 and 27 is
F
disabled.
P181: It indicates the contact state when digital output 2 to term. 29 and 31 is
disabled.
P187: It indicates the contact state when digital output 3 to term. 33 and 35 is
disabled.
P193: It indicates the contact state when digital output 4 to term. 37 and 39 is
disabled.
P199: It indicates the contact state when digital output 5 to term. 41 and 43 is
disabled.
0:Normally Open. When the output enables, the relevant relay energizes and
the contact on the relevant terminals closes.
1:Normally Closed. When the output enables, the relevant relay de-energizes
and the contact on the related terminals opens. See also figure in the
CONFIGURABLE DIGITAL OUTPUTS chapter.