P173(179)(185)(191)(197): Digital Output 1(2)(3)(4)(5) Switching Level - Santerno DCREG2 Series User Manual

Table of Contents

Advertisement

15P0059B3
USER MANUAL
7.2.74
P173(179)(185)(191)(197): D
S
W ITCHING
P... MDOxLevel
***
%
NOTE
NOTE
WARNING
158/200
L
EVEL
P
P173(179)(185)(191)(197) - MDO1(2)(3)(4)(5)Level
0 ... 200 %
R
P173: 50%
D
P179: 3 %
P185: 50%
P191: 5 %
P197: 50%
P173: Speed / voltage level, current level, error level or reference level for the
F
switching of digital output 1 to terminals 25 and 27 (if it is set according to one of
said indications).
P179: Speed / voltage level, current level, error level or reference level for the
switching of digital output 2 to terminals 29 and 31(if it is set according to one of
said indications).
P185: Speed / voltage level, current level, error level or reference level for the
switching of digital output 3 to terminals 33 and 35 (if it is set according to one of
said indications).
P191: Speed / voltage level, current level, error level or reference level for the
switching of digital output 4 to terminals 37 and 39 (if it is set according to one of
said indications).
P197: Speed / voltage level, current level, error level or reference level for the
switching of digital output 5 to terminals 41 and 43 (if it is set according to one of
said indications).
The digital output configured as 1:SpeedThreshold enables when the speed
absolute value in M001 (nFdbk) is higher than this parameter value. The
digital output configured as 2:AIarm Threshold enables when the current
absolute value in M004 (Iarm) - expressed as a percentage of the drive
armature nominal current, is higher than this parameter value. The digital
output configured as 8:Ifld Threshold enables when the current in M018 (Ifld) -
expressed as a percentage of the drive field nominal current - is higher than
this
parameter
value.
9:VrefThreshold enables when the speed error absolute value between the
Vref reference displayed on the KeyPad becomes higher than this parameter's
value. Finally, the digital input configured as 3:Motor at Speed enables when
the speed error absolute value between the ramp circuit input reference and
the speed / voltage feedback is lower than this parameter value. This means
that the actual speed has reached the programmed setpoint; i.e. the ramp
transient is over.
The level value set in these parameters cannot be lower than the value set in
MDOxHyst-type parameters.
To avoid any drive malfunction, never save a value lower than the one saved
in EEPROM for MDOxHyst-type parameters.
O
IGITAL
UTPUT
Similarly,
the
digital
DCREG2
DCREG4
1(2)(3)(4)(5)
output
configured
as