C102: Z
C102 ZeroingTime
***** msec
7.3.31
C103: E
C103 EmergStop
***
172/200
T
EROING
IME
P
C102 - ZeroingTime
30.00 ... 3000. ms
R
200.0 ms
D
Only if the inductive load type is selected, this parameter indicates the time
F
period (in milliseconds) after which both bridges are off when reversing.
S
MERGENCY
TOP
P
C103- EmergStop
0 ...1
R
1
D
This parameter defines the operating mode of the "STOP" key.
F
0:Included. Regardless of the command sources that have been selected,
pressing the "STOP" key determines the START digital input contact disable.
Speed will therefore decrease according to the ramp set in parameter P034
(RampStopPos) or P035 (RampStopNeg), depending on the reference polarity.
To restart the device, open and close the START digital input. In that case,
warning W005 (Open-Close START to run) is displayed.
1:Excluded. This key is active when at least one of the selected sources for the
command setting corresponds to KeyPad. For the interaction of this key with the
START digital inputs coming from other sources, see the Ref n section in the
BLOCK DIAGRAM chapter.