15P0059B3
USER MANUAL
7.3.37
C142: A
C142 A027 (SLink)
****
s
7.3.38
C143: A
C143 A028 (FBus)
****
s
7.3.39
C150: A
C150 A001 (Fld)
***
7.3.40
C151: A
C151 A004 (Load)
***
7.3.41
C153: A
C153 A006 (fUnst)
***
180/200
A027 T
LARM
RIP
P
C142 - A027(SLink)
1.00 ... 100. s
R
1.00 s
D
When the serial communication is selected as a reference or command source,
F
this parameter sets, in seconds, alarm A027 (Serial Link Failure) trip delay,
provided that no valid message has been sent.
A028 T
LARM
RIP
C143 - A028(FBus)
P
R
1.00 ... 100. s
D
1.00 s
F
When the field bus is selected as a reference or command source, this
parameter sets, in seconds, alarm A028 (FieldBus Failure) trip delay, provided
that no valid message has been sent.
A001 T
LARM
RIP
P
C150 - A001 (Fld)
0 ... 1
R
0
D
It inhibits alarm A001 (Field Failure) trip.
F
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.
A004 T
LARM
RIP
P
C151 - A004 (Load)
0 ... 1
R
0
D
It inhibits alarm A004 (Load Loss).
F
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.
A006 T
LARM
RIP
P
C153 - A006(fUnst)
R
0 ... 1
D
0
It inhibits alarm A006 (Unstable Frequency).
F
0:Included. The alarm is enabled.
1:Excluded. The alarm is disabled.
D
ELAY
D
ELAY
D
ISABLING
D
ISABLING
D
ISABLING