C094: Startsafety; C100: Local / Mixed Selection Enabling; C101: Delay From Starting Enabling - Santerno DCREG2 Series User Manual

Table of Contents

Advertisement

DCREG2
DCREG4
7.3.27
C094: S
C094 StartSafety
***
7.3.28
C100: LOCAL / MIXED S
C100 LocRemSel
***
NOTE
7.3.29
C101: D
C101 PwrOnTime
****
sec
S
TART
AFETY
P
C094 - StartSafety
0 ... 1
R
0
D
When the cause of the alarm trip has disappeared and a manual or automatic
F
reset of the alarm has been performed, this parameter determines whether a
safety preventing the drive to automatically and immediately restart should be
enabled. Of course, this function is active only if the device is actually able to
restart (no alarm detected, power section properly supplied, ENABLE and
START digital inputs closed).
0:No. Device self-start enabled when no alarm conditions are detected, after the
reset or when the power supply is restored.
1:Yes. The device is not allowed to restart by itself when no alarm conditions
are detected, after the reset or when the power supply is restored. By contrast, it
may be restarted only after the ENABLE digital input temporary activation and
deactivation. In that case, warning W004 is displayed (Open-Close ENABLE to
run).
P
C100 - LocRemSel
0 ... 1
R
0
D
This parameter allows the drive switching from the MIXED mode (i.e. from
F
terminal board, serial communication, field bus or keypad) to the LOCAL mode
only (i.e. from keypad only) and vice versa, by simultaneously pressing the "  "
and "SAVE" keys.
0:Enabled. Switching (obtained by pressing the two above mentioned keys
simultaneously) enabled.
1:Disabled. Switching (obtained by pressing the two above mentioned keys
simultaneously) disabled.
This parameter may be used to avoid an accidental switching of the drive
operation trough the keypad.
In any operating mode, the drive running procedure always requires the ENABLE
contact closing on terminal 24.
S
ELAY FROM
TARTING
P
C101 - PwrOnTime
0.00 ... 10.0 s
R
10.0 s
D
Only if the inductive load type is selected, this parameter indicates the delay
F
time (in seconds) from the application of supply voltage to the control section
before the first start command is sent.
E
ELECTION
NABLING
E
NABLING
15P0059B3
USER MANUAL
171/200