C130(131)(132)(133)(134)(135): Digital Input 1(2)(3)(4)(5)(6) Configuration - Santerno DCREG2 Series User Manual

Table of Contents

Advertisement

DCREG2
DCREG4
7.3.35
C130(131)(132)(133)(134)(135): D
1(2)(3)(4)(5)(6) C
C... MDIxCfg
***
ONFIGURATION
P
C130(131)(132)(133)(134)(135) - MDI1(2)(3)(4)(5)(6)Cfg
0 ... 20
R
C130: 0
D
C131: 12
C132: 13
C133: 1
C134: 4
C135: 5
C130: It indicates the configuration of programmable digital input 1 (MDI 1)
F
(terminal 28 if the terminal board is selected).
C131: It indicates the configuration of programmable digital input 2 (MDI 2)
(terminal 30 if the terminal board is selected).
C132: It indicates the configuration of programmable digital input 3 (MDI 3)
(terminal 32 if the terminal board is selected).
C133: It indicates the configuration of programmable digital input 4 (MDI 4)
(terminal 34 if the terminal board is selected).
C134: It indicates the configuration of programmable digital input 5 (MDI 5)
(terminal 36 if the terminal board is selected).
C135: It indicates the configuration of programmable digital input 6 (MDI 6)
(terminal 38 if the terminal board is selected).
0:Reset. When the input closes, it enables deleting the alarm previously stored.
This is equivalent to simultaneous pressing the "PROG" and "SAVE" keys.
1:Preset Speed A. When the input closes, it selects - in conjunction with other
digital inputs programmed with the 2:Preset Speed B and 3:Preset Speed C
functions - a preset run reference among all references programmed in
parameters P211 ... P217, according to the matching table contained in the
section relating to said parameters.
2:Preset Speed B. When the input closes, it selects - in conjunction with other
digital inputs programmed with the 1:Preset Speed A and 3:Preset Speed C
functions - a preset run reference among all references programmed in
parameters P211 ... P217, according to the matching table contained in the
section relating to said parameters.
3:Preset Speed C. When the input closes, it selects - in conjunction with other
digital inputs programmed with the 1:Preset Speed A and 2:Preset Speed B
functions - a preset run reference among all references programmed in
parameters P211 ... P217, according to the matching table contained in the
section relating to said parameters.
4:Clim. When the input closes, it enables decreasing the actual current limit for
both bridges according the value per cent programmed in P058 (Clim).
5:Reverse. When the input closes, it reverses polarity for the Ref n reference
applied to the ramps (including the preset run references and the internal jog
references), and for the references on auxiliary inputs, provided that they are
configured as speed references.
6:Slave Enabled. When the input closes, it disables the speed loop; the same
function is obtained if parameter C050 is programmed as 3:Iref=Vref. As a
consequence, the current reference is supplied by the Main Ref or by one of the
preset run references or by one of the internal jog references, summed to
references IN 1, IN 2 and IN 3, provided that they have been configured as
additional current references. However, the current reference enters the control
loop with no ramp or rounding, even though they have been programmed in
parameters P030 ... P039.