Each FE PDU has one power inlet port (input connector) and three power outlet ports. The power
outlet ports are IEC 320-C19 ports, with 16 amp rating. Depending on the inlet cord type, you can
connect up to three BE PDU. There are two types of input connectors for each region.
• In non-EMEA countries, you can use two outlet ports only with an L6-30P connector for 30 amp
connectivity. You can use all outlet ports with an IEC 309-60A connector. Only 48 AMPs are
required.
• In EMEA countries, you can use two outlet ports only with an IEC 309-32A connector for 30
amp connectivity. All outlet ports can be used with an IEC 309-63A connector.
Note:
You can connect the Ethernet Routing Switch (ERS formally Passport) series 8000 switch
to FE PDU on systems with three FE PDU. See
more information.
• The Hubbell P/N for the connector is the 363P6W.
PDU Position
The FE PDU position in the cabinet depends on power considerations at the customer site. In most
instances, the power is supplied from the bottom of the cabinet and the FE PDU is situated there.
The input connector to the FE PDU faces the interior of the cabinet. This is to provide sufficient
clearance between the FE PDU and the cabinet mounted equipment. Refer to your System
Definition Package for the exact location of the PDU in your installation.

BE PDU

The following diagram shows two BE PDU.
October 2014
Avaya Media Processing Server 1000 Hardware Installation and Maintenance