StorEdge-related Errors Codes

StorEdge-related Errors Codes
This section describes the error messages that are specific to the StorEdge solution. For the general SolarEdge troubleshooting refer to the codes in the previous 
section. 
CPU v3.18
and below
179, 180
181
183
184
185
SolarEdge-StorEdge -Single Battery/High Capacity Installation MAN-01-00283-1.1
Error code
LCD message
CPU v3.19
and above
Backup Consumption
2xB3, 2xB4
Too High
Connection Unit
2xB5
HW Error
Connection Unit
2xB7
Communication Error
Connection Unit
2xB8
Temp. Too High
3x6B
Meter Comm. Error
Cause and Troubleshooting
Inverter production stopped due to backed-up loads'
consumption exceeding product rating.
Shutdown non-essential loads to reduce power
consumption.
Check all the communication cable between the StorEdge
Connection Unit and the digital board in the inverter.
There is a faulty wire connection or an internal error.
Check the communication cable between the
o
StorEdge Connection Unit and the digital board in the
inverter.
Check that the StorEdge Connection Unit LEDs are
o
ON.
Inverter production stopped due to StorEdge Connection
Unit overheating or due to internal fan malfunction.
Clean the StorEdge Connection Unit fan
o
If the fan is malfunctioning, replace the fan
o
Refer to Meter Troubleshooting on page 82.