StorEdge-related Errors Codes

StorEdge-related Errors Codes
This section describes the error messages that are specific to the StorEdge solution. For 
troubleshooting errors that are not listed below, refer to 
https://www.solaredge.com/sites/default/files/troubleshooting_for_se_inverter_
insallation_guide_addendum_na.pdf contact SolarEdge support. For the general 
SolarEdge troubleshooting refer to the codes in the previous section. 
Error code
CPU v3.18
CPU v3.19
and below
and above
178
3x6D
179, 180
2xB3, 2xB4
181
2xB5
182
2xB6
183
2xB7
184
2xB8
185
3x6B
186
3x6B
100
LCD message
Internal RGM Error
Check the CTs connections and direction.
Inverter production stopped due to backed-up loads'
Backup Consumption
consumption exceeding product rating.
Too High
Shutdown non-essential loads to reduce power
consumption.
Connection Unit
Check all the communication cable between the
Connection Unit and the digital board in the inverter.
HW Error
Inverter production stopped due to auto-transformer
overheating.
Shutdown non-essential loads to reduce the phase
Auto-Transformer
imbalance.
Temp. Too High
If you use the inverter for on-grid applications only
(without auto-transformer) - move SW2 to the
UP position (ON) (refer to DIP Switch Setup on page
38).
There is a faulty wire connection or an internal error.
o
Connection Unit
Communication Error
o
Inverter production stopped due to Connection Unit
overheating or due to internal fan malfunction.
Connection Unit
Temp. Too High
o
o
Meter Comm. Error
Refer to Meter Troubleshooting on page 94.
o
Battery Comm Error
o
o
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.3
Cause and Troubleshooting
Check the communication cable between the
Connection Unit and the digital board in the
inverter.
Check that the Connection Unit LEDs are ON.
Clean the Connection Unit fan
If the fan is malfunctioning, replace the fan
Check the wiring to the battery and the battery
DIP switch configuration (refer to Connecting to
the Battery on page 34 and DIP Switch Setup on
page 38.
Connecting to the Battery on page 34
Check the battery setup in the RS485-Conf screen
(refer to Configuring the RS485 Bus for Battery
and Meter Connection on page 82).