General Inverter Error Codes - SolarEdge StorEdge SE5000-xxS0 series Installation Manual

For single battery or high capacity
Table of Contents

Advertisement

General Inverter Error Codes

General Inverter Error Codes
Error # Single Phase
Error # Three Phase
CPU v3.18
CPU v3.19
CPU v3.18
and below
and above
and below
4, 5, 8, 18-
2x13, 2x15,
45, 48, 50-
23, 39, 42,
2x16, 3x2,
53, 94, 107-
45, 48
2x2D, 3xF
111,113
N/A
112
9, 13
2x9, 2xD
N/A
2xA, 2x25,
10, 37, 38
76, 77, 90
2x26
SolarEdge-StorEdge -Single Battery/High Capacity Installation MAN-01-00283-1.1
LCD
Message
CPU v3.19
and above
3x2,3xF, 8x11 -
8x13, 8x3D,
SW Error
8x4A - 8x4E,
8x50
Wrong AC
8x4F
connection
AC Current Surge
Vac surge
8x2B, 8x2C,
Ground Current -
8x39
RCD
Cause and Troubleshooting
Contact SolarEdge Support.
Switch between L1 and L2 or L2 and L3 connections
Ground current surge.
Check the AC connection to the inverter
o
Check with the grid operator if a large surge source or irregular load exists near the
o
site.
If the grid does not have problems contact SolarEdge support.
o
Ground faults may occur due to insufficient insulation to the ground.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not
touch uninsulated wires when the inverter
cover is removed.
Only a qualified technician should handle this problem, and only after taking proper
precautions.
1. Turn the inverter ON/OFF switch to OFF.
2. Wait five minutes for the input capacitors to discharge.
3. Disconnect the AC breaker.
4. Disconnect the DC inputs.
89