Measure the necessary length between the StorEdge Connection Unit and the battery for all cables. 
l
The maximum distance between the battery and the inverter is 35 ft/ 10m, when using 16AWG/ 
2
1.3mm
 cables for battery thermal power and 24AWG/0.2mm
Tie and wrap the cables   t o avoid pulling them out during mounting.
l
Be sure to adhere to all safety cautions and information in the battery documentation. 
l
The battery   c onnects to the DC side of the inverter. Since the inverter DC connections are on its left 
l
side, it is recommended to position the battery   t o the left of the inverter to simplify wiring.
The following table and Figure 21 detail cable types and connections of one battery (Tesla PowerWall Type 
B/B1). For additional battery types and connection options, refer to Additional Battery Connections on 
page 75. Prepare cables and connect as described in the following table :
Recommended cable type
(min-max cross section)
DC
2
DC cable 6mm
(4-10 mm
insulated.
12V thermal power input
2-wire shielded pair cable 1.5 mm
2
(1.3 - 2.5 mm
), 600V insulated
Control and monitoring
5-wire shielded twisted pair cable
2
2
0.2 mm
(0.2 - 1.5 mm
), 600V
insulated.
A CAT5 600V insulated can also
be used.
1 Must be twisted pair
SolarEdge-StorEdge -Single Battery/High Capacity Installation MAN-01-00283-1.1
StorEdge
Connection
Unit
connection
2
), 600V
BAT IN DC +
BAT IN DC-
Battery
Thermal V-
2
(black)
Battery
Thermal V+
(red)
5-pin
communication
terminal block:
En (Enable)
V+
G (RS485)
1
B- (RS485)
1
A+ (RS485)
Chapter 5: StorEdge Inverter Connections
2
 for battery control.
Tesla battery
connection
DC+
Inverter side: Connect to the
BAT IN connectors
DC-
Insert the cable through one of the large
THERMAL -
openings in the gland.
Push the lever to open the connection,
insert the wire and release the lever
THERMAL +
when the wire is clamped.
communication port
1 (located closer to
Insert the cable through one of the large
the DIP switches):
openings in the gland.
ENABLE
Press the protrusion at the top of the
terminal block to open the connection
LOGIC +
hole, insert the wire and release to
LOGIC -
spring back and clamp the wire.
1
COM LO
1
COM HI
Connection method