Emission Requirements; Immunity Requirements - Danfoss VLT AQUA Drive FC 202 Design Manual

Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

System Integration

3.2.3 Emission Requirements

The EMC product standard for adjustable frequency drives
defines four categories (C1, C2, C3 and C4) with specified
3
3
requirements for emission and immunity. Table 3.5 states
the definition of the four categories and the equivalent
classification from EN 55011.
Category
Definition
C1
Adjustable frequency drives
installed in the first environment
(home and office) with a supply
voltage less than 1000 V.
C2
Adjustable frequency drives
installed in the first environment
(home and office) with a supply
voltage less than 1000 V, which are
neither plug-in nor movable and
are intended to be installed and
commissioned by a professional.
C3
Adjustable frequency drives
installed in the second
environment (industrial) with a
supply voltage lower than 1000 V.
C4
Adjustable frequency drives
installed in the second
environment with a supply voltage
equal to or above 1000 V or rated
current equal to or above 400 A or
intended for use in complex
systems.
Table 3.5 Correlation between IEC 61800-3 and EN 55011
When the generic (conducted) emission standards are
used, the adjustable frequency drives are required to
comply with the limits in Table 3.6.
Environment
First
environment
(home and
office)
Second
environment
(industrial
environment)
Table 3.6 Correlation between Generic Emission Standards and
EN 55011
48
VLT
Equivalent
emission class
in EN 55011
Class B
Class A Group 1
Class A Group 2
No limit line.
Make an EMC
plan.
Equivalent
Generic emission
emission class in
standard
EN 55011
EN/IEC 61000-6-3 Emission
Class B
standard for residential,
commercial and light
industrial environments.
EN/IEC 61000-6-4 Emission
Class A Group 1
standard for industrial
environments.
Danfoss A/S © 09/2014 All rights reserved.
®
AQUA Drive FC 202

3.2.4 Immunity Requirements

The immunity requirements for adjustable frequency drives
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and office
environment. All Danfoss adjustable frequency drives
comply with the requirements for the industrial
environment and consequently comply also with the lower
requirements for home and office environment with a
large safety margin.
To document immunity against electrical interference, the
following immunity tests have been made in accordance
with following basic standards:
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
communication equipment as well as mobile
communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Electrical
interference: Simulation of interference brought
about by switching a contactor, relay or similar
devices.
EN 61000-4-5 (IEC 61000-4-5): Surge transients:
Simulation of transients brought about, for
example, by lightning that strikes near instal-
lations.
EN 61000-4-6 (IEC 61000-4-6): RF Common
mode: Simulation of the effect from radio-
transmission equipment joined by connection
cables.
See Table 3.7.
MG20N622