Wiring the bus connector
1. Proceed as follows to connect the bus connector:
2. Plug the bus connector into the corresponding interface on the NCU.
3. Screw the bus connector into place.
Figure 7-10
7.8.6

Disconnecting stations from the PROFIBUS

Removing the bus connector
You can remove the bus connector with a looped-through bus cable from the PROFIBUS DP
interface at any time without interrupting data traffic on the bus.
NOTICE
Data exchange on the bus can be interrupted!
A bus segment must always be terminated with the terminating resistor at both ends. This is
not the case, for example, if the last node with a bus connector is de-energized. Because the
bus connector takes its voltage from the node, this terminating resistor is ineffective.
Make sure that the nodes at which the terminating resistor is connected are always energized.
7.8.7

Operating the X136 interface as MPI

Applications
The X136 interface can also be operated as an MPI interface instead of a PROFIBUS DP
interface. 187.5 kbit/s is the typical (preset) data rate. A maximum data rate of 12 Mbit/s can
be set to communicate with other CPUs. However, it should be noted that the maximum data
rate is not supported by all CPUs (e.g. smaller SIMATIC S7 CPUs).
NCU 7x0.3 PN, NCU 7x0.3B PN
Manual, 06/2014, 6FC5397-1EP40-5BA1
As the NCU is located at the start or end of a segment, you must switch on the terminating
resistor ("ON" switch setting).
Terminating resistor switched on and off
Note
Make sure that the stations on which the terminating resistor is located are always supplied
with voltage during booting and operation.
Connecting
7.8 PROFIBUS DP
69