Description of AS-i profiles used with DMS

Bit Type for host
D0
output
Run forward
D1
output
Run reverse
D2
output
D3
output
Fault reset
D0
input
D1
input
D2
input
D3
input
P0
parameter
P1
parameter
P2
parameter
P3
parameter
It is possible to operate DMS with both the control
inputs and an AS-i Interface. It will function as follows:
Start CW: Logically "OR"ed - DMS will Start
if either input is active.
Start CCW: Logically "OR"ed - DMS will Start
if either input is active.
Brake: Logically "OR"ed - DMS will generate Brake
release command if either input is active.
Reset/Coasting stop inverse: Logically "AND"ed.
NOTE
Both inputs must be active for DMS to Start.
If AS-i bus is used for control, the binary
Reset/Coasting stop inverse input must be
held active (i.e. connected to +24 VDC)
Configuring DMS with a Slave address:
54
Host
Meaning
level
0
1
0
1
0
Brake
1
0
1
0
Not ready or fault
Ready
1
0
Running
1
0
Fault
1
0
Not used
1
Not used
Not used
Not used
Not used
Direct starter with
Direct starter
Profile 7E 1
Stop - forward
Stop - forward
Start - forward
Start - forward
Not used
Motor blocked
Not used
Not reset
Reset
Not ready or fault
Ready
Motor stopped
Motor stopped
Motor running
No fault
Fault
Not used
Use a standard AS-i addressing device or the AS-i
master to configure the DMS with the designated
slave address on the AS-i network.
MG.90.F2.22 - VLT is a registered Danfoss trademark
Decentral Solutions
Reverser with brake
brake
Profile 7E 3
Stop - forward
Start - forward
Stop - reverse
Not used
Start - reverse
Motor blocked
Motor free
Not reset
Reset
Not ready or fault
Ready
Motor stopped
Motor running
No fault
Fault
Not used
Profile 7E 4
Motor free
Not reset
Reset
Ready
Motor running
No fault
Fault
Not used