Danfoss VLT DMS 300 Manual page 103

Table of Contents

Advertisement

External reference [%] gives the sum of external
references as a percentage (sum of analog/pulse/serial
communication) in the range from Minimum reference,
Ref
to Maximum reference, Ref
MIN
Status word [Hex] gives one or several status
conditions in a Hex code. See Serial communication
in the Design Guide for further information.
Heat sink temp.[°C] gives the present heat sink
temperature of the variable frequency drive. The
cut-out limit is 194-212 °F (90-100 °C), while cutting
back in occurs at 158 ± 10% °F (70 ± 5 °C).
Alarm word [Hex] gives one or several alarms
in hex code. See Serial communication in the
Design Guide for further information.
Control word [Hex] gives the control word for the
variable frequency drive. See Serial communication
in the Design Guide for further information.
Warning word [Hex] gives one or several warnings
in hex code. See Serial communication in the
Design Guide for further information.
Extended status word [Hex] gives one or several status
modes in Hex code. See Serial communication in
the Design Guide for further information.
Communication option card warning [Hex] gives a
warning word if there is a fault in the communication
bus. Only active if communication options are installed.
If there are no communication options 0
Hex is displayed.
Pulse input 29[Hz] gives the frequency in Hz
connected to terminal 29.
Pulse count gives the number of pulses that
the unit has registered.
010 Small display line 1.1
(DISPLAY LINE 1.1)
Value:
See par. 009 Large display readout
Function:
In this parameter, the first of three data values
can be selected that is to be displayed in the LCP
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark
control unit display, line 1, position 1. This is a useful
function, e.g. when setting the PID regulator, as
it gives a view of process reactions to reference
changes. The display readout is activated by
.
MAX
pushing the [DISPLAY STATUS] key.
See parameter 009 Large display readout.
See parameter 009 Large display readout
See the functional description given under parameter
010 Small display readout.
See parameter 009 Large display readout.
See parameter 009 Large display readout
See the functional description given under parameter
010 Small display readout.
See parameter 009 Large display readout.
Reference [%] [1]
Decentral Solutions
Description of choice:
011 Small display readout 1.2
(DISPLAY LINE 1.2)
Value:
Function:
Description of choice:
012 Small display readout 1.3
(DISPLAY LINE 1.3)
Value:
Function:
Description of choice:
013 Local control
(LOC CTRL/CONFIG.)
Value:
Local not active (DISABLE)
Local control and open loop
(LOC CTRL/OPEN LOOP)
Remote-operated control and open loop
(LOC+DIG CTRL)
Local control as parameter 100
(LOC CTRL/AS P100)
Remote-operated control as parameter 100
Motor current [A][6]
Power [kW][8]
[0]
[1]
[2]
[3]
103