Bit 00, Control not ready/ready:
Bit 00 = '0' means that the Bit 00, 01 or 02 in the
control word are '0' (OFF1, OFF2 or OFF3) or the
variable frequency drive is not ready for operation.
Bit 00 = '1' means that the variable frequency
drive is ready for operation.
Bit 01, Drive ready:
See description under Status word according
to FC protocol.
Bit 02, Coasting stop:
Bit 02 = '0' means that Bits 00, 02 or 03 in the control
word are "0" (OFF1, OFF3 or Coasting stop).
Bit 02 = '1' means that Bits 00, 01, 02 and 03
in the control word are "1", and that the variable
frequency drive has not tripped.
Bit 03, No trip/trip:
See description under Status word according
to FC protocol.
Bit 04, ON 2/OFF 2:
Bit 04 = '0' means that Bit 01 in the control word = '1'.
Bit 04 = '1' means that Bit 01 in the control word = '0'.
Bit 05, ON 3/OFF 3:
Bit 05 = '0' means that Bit 02 in the control word = '1'.
Bit 05 = '1' means that Bit 02 in the control word = '0'.
Bit 06, Start enable/start disable:
Bit 06 = '1' after reset of a trip, after activation of OFF2
or OFF3 and after connection of AC line voltage. Start
MG.90.F2.22 - VLT is a registered Danfoss trademark
disable is reset by setting Bit 00 in the control word
Bit =1
to '0', and Bit 01, 02 and 10 are set to '1'.
Control ready
Drive ready
Bit 07, Warning:
See description under Status word according
Trip
to FC protocol.
OFF 2
OFF 3
Bit 08, Speed:
Start disable
See description under Status word according
Warning
to FC protocol.
Speed = ref.
Ser. communi.
Bit 09, No warning/warning:
Frequency limit
See description under Status word according
OK
to FC protocol.
Motor running
Bit 10, Speed ≠ ref/speed = ref.:
Voltage warn.
See description under Status word according
Current limit
to FC protocol.
Thermal warn.
Bit 11, Running/not running:
See description under Status word according
to FC protocol.
Bit 13, Voltage warning high/low:
See description under Status word according
to FC protocol.
Bit 14, Current limit:
See description under Status word according
to FC protocol.
Bit 15, Thermal warning:
See description under Status word according
to FC protocol.
Serial communication reference
The serial communication reference is transferred to
the variable frequency drive as a 16-bit word. The value
is transferred in whole numbers 0 - ±32767 (±200%).
16384 (4000 Hex) corresponds to 100%.
The serial communication reference has the following
format: 0-16384 (4000 Hex)
Minimum ref. - Par. 205 Maximum ref.).