Danfoss VLT DMS 300 Manual page 164

Table of Contents

Advertisement

505 Start
(START SELECT)
Value:
Digital input (DIGITAL INPUT)
Serial port (SERIAL PORT)
Logic and (LOGIC AND)
Logic or (LOGIC OR)
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor has stopped
and when the variable frequency drive has a start
command when each of the following is selected: Digital
input [0], Serial port [1], Logic and [2] or Logic or [3].
Digital input [0]
Dig. input
Ser. port
0
0
0
1
1
0
1
1
Serial port [1]
Dig. input
Ser. port
0
0
0
1
1
0
1
1
Logic and [2]
Dig. input
Ser. port
0
0
0
1
1
0
1
1
Logic or [3]
Dig. input
Ser. port
0
0
0
1
1
0
1
1
= factory setting. () = display text [] = value for use in communication via serial communication port
164
506 Reverse
Value:
[0]
Digital input (DIGITAL INPUT)
[1]
Serial port (SERIAL PORT)
[2]
Logic and (LOGIC AND)
[3]
Logic or (LOGIC OR)
Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is running
clockwise and counter-clockwise when each of
the following is selected: Digital input [0], Serial
port [1], Logic and [2] or Logic or [3].
Digital input [0]
Function
Dig. input
Stop
Stop
Start
Start
Serial port [1]
Function
Dig. input
Stop
Start
Stop
Start
Logic and [2]
Function
Dig. input
Stop
Stop
Stop
Start
Logic or [3]
Function
Dig. input
Stop
Start
Start
Start
Decentral Solutions
(REVERSE SELECT)
Ser. port
0
0
0
1
1
0
1
1
Ser. port
0
0
0
1
1
0
1
1
Ser. port
0
0
0
1
1
0
1
1
Ser. port
0
0
0
1
1
0
1
1
MG.90.F2.22 - VLT is a registered Danfoss trademark
[0]
[1]
[2]
[3]
Function
Clockwise
Clockwise
Counter-clockwise
Counter-clockwise
Function
Clockwise
Counter-clockwise
Clockwise
Counter-clockwise
Function
Clockwise
Clockwise
Clockwise
Counter-clockwise
Function
Clockwise
Counter-clockwise
Counter-clockwise
Counter-clockwise