Safeguards:
Electronic thermal motor protection against overload.
Temperature monitoring of the power module ensures that the adjustable frequency drive cuts
out if the temperature reaches 212 °F (100 °C). An overload temperature cannot be reset until
the temperature of the power module is below 160 °F (70 °C).
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If an electrical phase is missing, the variable frequency drive will cut out.
Monitoring of the intermediate circuit voltage ensures that the variable frequency drive cuts out
if the intermediate circuit voltage is too low or too high.
The variable frequency drive is protected against ground fault on motor terminals U, V, W.
198