Select Special motor mode [8], if a special U/f setting
is needed that is to be adapted to the present
motor. The break points are set in parameters
423-428 Voltage/frequency .
NOTE
Please note that if a value set in the nameplate
parameters 102-106 is changed, there will
be an automatic change of parameter 108
Stator resistance and 109 Stator reactance.
102 Motor power P
M,N
(MOTOR POWER)
Value:
0.18 - 4 kW
Function:
Here you must set a power value [kW] P
corresponding to the motor's rated power. The
factory sets a rated power value [kW] P
depends on the type of unit.
Description of choice:
Set a value that matches the nameplate data on the
motor. Settings between two sizes below and one
size over the factory setting are possible.
103 Motor voltage U
M,N
(MOTOR VOLTAGE)
Value:
50 - 999 V
Function:
This is where to set the rated motor voltage U
for either star Y or delta
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark
Depends on unit
,
M,N
, that
M,N
400 V
M,N
.
Decentral Solutions
Description of choice:
Select a value that corresponds to the nameplate
data on the motor, regardless of the variable
frequency drive's AC line voltage.
104 Motor frequency f
(MOTOR FREQUENCY)
Value:
24-1000 Hz
Function:
This is where to select the rated motor frequency f
Description of choice:
Select a value that corresponds to the nameplate
data on the motor.
105 Motor current I
M,N
(MOTOR CURRENT)
Value:
0,01 - I
Depends on choice of motor
MAX
Function:
The nominal, rated current of the motor I
of the variable frequency drive calculation of features
such as torque and motor thermal protection.
Description of choice:
Set a value that corresponds to the nameplate data
on the motor. Set the motor current I
into account whether the motor is star-connected
Y or delta-connected
.
106 Rated motor speed
(MOTOR NOM. SPEED)
Value:
100 - f
x 60 (max. 60000 rpm)
M,N
Depends on parameter 102 Motor power, P
Function:
This is where to set the value that corresponds
to the rated motor speed n
from the nameplate data.
M,N
50 Hz
.
M,N
forms part
M,N
taking
M,N
M,N
that can be seen
M,N
109