Description Of As-I Profiles Used With Dms - Danfoss DMS 300 Operating Instructions Manual

Decentral motor starter
Table of Contents

Advertisement

Description of AS-i profiles used with DMS

Bit Type for host
Meaning
D0
output
Run forward
D1
output
Run reverse
D2
output
Brake
D3
output
Fault reset
D0
input
Ready
D1
input
Running
D2
input
D3
input
Not used
P0
parameter
Not used
P1
parameter
Not used
P2
parameter
Not used
P3
parameter
Not used
It is possible to operate DMS with both the control
inputs and an AS-i Interface. It will function as follows:
Start CW: Logically "OR"ed – DMS will Start
if either input is active.
Start CCW: Logically "OR"ed – DMS will
Start if either input is active.
Brake: Logically "OR"ed – DMS will generate Brake
release command if either input is active.
Reset/Coasting stop inverse: Logically "AND"ed.
NB!:
Both inputs must be active for DMS to Start.
If AS-i bus is used for control, the binary
Reset/Coasting stop inverse input must be
held active (i.e. connected to +24 VDC)
Configuring DMS with a Slave address:
Use a standard AS-i addressing device or the AS-i
master to configure the DMS with the designated
slave address on the AS-i network.
MG.05.A2.02 - VLT is a registered Danfoss trademark
Host
Direct starter
level
Profile 7E 1
0
Stop - forward
1
Start - forward
0
Not used
1
0
Not used
1
0
Not reset
1
0
Not ready or fault
1
0
Motor stopped
1
Motor running
0
Fault
1
0
Not used
1
DMS Manual
Direct starter with
brake
Profile 7E 3
Stop - forward
Start - forward
Not used
Motor blocked
Motor free
Not reset
Reset
Reset
Not ready or fault
Ready
Ready
Motor stopped
Motor running
No fault
No fault
Fault
Fault
Not used
Reverser with brake
Profile 7E 4
Stop - forward
Start - forward
Stop - reverse
Start - reverse
Motor blocked
Motor free
Not reset
Reset
Not ready or fault
Ready
Motor stopped
Motor running
No fault
Fault
Not used
13