Programming the user functions
11.6.3 Step 3, change the function of the remote transmission
Change the function of contact 1
Select
Option
Function
KEY13
1 (default)
Active during "Released" to "Reset" state
▼
2
Active during "Activated" or "Released" to "Reset" state
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
3
step 11 option 9, 10 or 12) to "Reset" state
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
4
step 11 option 9 or 10 or 12) or "Activated" or "Released" to "Reset"
state
Change the function of contact 3
Select
Option
Function
KEY13
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
5 (default)
▼
step 11 option 9 or 12) to "Reset" state
Active during "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
6
step 11 option 9 or 12) or "Activated" to "Reset" state
7
Active during "Emergency hold/abort" until the cause is eliminated
Change the function of contact 2
Select
Option
Function
KEY14
8 (default)
Active during "Fault" to "Silence buzzer" state
▼
Active during "Fault" state until the cause is eliminated and "Silence
9
buzzer"
10 (default) Immediate triggering
11
3 minutes delay in "Buzzer not silenced" state (*)
Change the function of LED9 (Remote transmission) and LED6 (Fire alarm)
Select
Option
Function
KEY15
12 (default) LED9: Active only in "RT-alarm" (*) state
▼
13
LED9: Active in "RT-alarm" (*) and "RT-fault" (**) state
14
LED9: Inoperative (LED23, LED25 and KEY12 without function)
15 (default) LED6: Active on Alarm Z1 or Z2 or Z3
16
LED6: Active on "Activated" if activated is initiated by detectors
(*)
(**) Function dependent on option 8 and 9
Change the function of control line 2
Select
Option
Function
17 (default) Active on state "RT-alarm" to "Reset" (*)
KEY16
▼
Processing as "RT-alarm"
18
Active on state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed
in step 11 option 9, 12 or 13), "Activated" and "Released" to "Reset"
Processing as "Fire control"
19
Active on state "Activated" and "Released" to "Reset"
Processing as "Fire control"
20
Active on state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed
in step 11 option 9, 10, 12 or 13), "Activated" and "Released" to
"Silence Re-sound horn" or "Reset"
Processing as "Horn"
21
Active on state "Activated" and "Released" to "Silence Re-sound
Horn" or "Reset"
Processing as "Horn"
22
Active on state "Mech. blocked"
Processing as "Warning panel"
23
Active on state "Autom. & Man. blocked"
Processing as "Warning panel"
24
Active on state "Manual only" or "Autom. & Man. blocked"
Processing as "Warning panel"
(*)
78
Building Technologies
Fire Safety & Security Products
Function dependent on option 1 to 4
Function of dependent on option 1 to 4
Zone 1
Zone 2
Zone 3
Red
Yel. Red Yel. Red Yel. Red Yel.
–
Zone 1
Zone 2
Zone 3
Yel.
Red
Red Yel. Red Yel. Red Yel.
–
Zone 2
Zone 1
Zone 3
Red Yel.
Red Yel.
Red Yel. Red Yel.
–
–
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red Yel.
–
–
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel.