Application Limitations; Specified Standards And Options - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

System overview
3.1

Application limitations

3.2

Specified standards and options

EN12094-1
Basic functions
Options and the associated requirements
4.17
Delay of extinguishing signal
4.18
Signal representing the flow of extinguishing
agent
4.19
Monitoring of the status of components
Loss of agent
Non-electrical blocking device
4.20
Emergency hold
4.21
Control of flooding time
4.22
Initiation of secondary flooding
4.23
Manual only mode
4.24
Triggering signals to equipment within the
system
Extinguishing signals to spare cylinders
4.25
Triggering of equipment outside the system
4.26
4.27
Emergency abort
4.28
Control of extended discharge
4.29
Release of the extinguishing media for selected
flooding
4.30
Activation of alarm devices with different signals
EN54-2
Basic functions
Options and associated requirements
7.8
Output to fire alarm device in accordance with
EN54-1 / C
7.9
Output to fire alarm routing equipment in
accordance with EN54-1 / E
7.10
Output to fire protection equipment or in
accordance with EN54-1 / G
Delay to outputs
7.11
Coincidence detection
7.12
Alarm counter
7.13
Fault signals from points
8.3
8.4
Total loss of the power supply
8.9
Output to fault warning routing equipment in
accordance with EN54-1 / J
10
Test condition
12
Building Technologies
Fire Safety & Security Products
no monitored remote control panel
not usable for multi-sector installations with electrical cylinder allocation and full
redundancy
no provision to monitor a spare cylinder bank
no facility for secondary flooding control (low pressure installations)
no interface for VdS peripherals such as FBF, ÜE, FSD, SST
Related XC10 configuration
Monitored control line 4, programming step 1 option 1-13
Monitored input 1, programming step 4 option 1
Monitored input 1A (XCA1016) programming step 4 option 1
Monitored input 2, programming step 4 option 10
Monitored input 1B (XCA1016) programming step 4 option 1
Monitored input 2, programming step 4 option 6
Monitored input 3, programming step 8 option 2
Key "Mode select"
Monitored input 3, programming step 8 option 6
Monitored control line 3, programming step 5 option 15-25
Driver output 1 and 2
Monitored control line 5, programming step 1 option 17
Monitored input 3, programming step 8 option 1
Monitored control line 1, programming step 5 option 1-10
Related XC10 configuration
Monitored control line 1, programming step 5 option 1-10
Monitored control line 2, programming step 3 option 17
Monitored control line 2, programming step 3 option 18 or 19
Detector zones 1, 2 and 3, programming step 6 option 1-4
Separate wire from battery to upper main board XCM1001-2
Potential-free contact Nr. 2, programming step 3 option 8-11
Fulfilled
x
x
x
x
x
-
-
x
x
-
x
x
-
-
x
Fulfilled
x
x
x
x
-
x
-
x
x
x
x
A6V10099837_a_en
12.2007