LED14 / Yellow
Loss of agent
LED15 / Yellow
Earth fault
LED16 / Yellow
Power fault
LED17 / Yellow
Peripheral fault
LED18 / Yellow
System fault
LED19 / Yellow
System test
LED20 / Yellow
Horn/Actuator
LED21 / Red
-
LED22 / Yellow
Fire control
LED23 / Yellow
RT-fault
LED24 / Red
-
LED25 / Yellow
RT-alarm
LED26 / Yellow
Emergency
Hold/Abort
Building Technologies
Fire Safety & Security Products
Indicator elements (LED1 to LED34)
Fast
Monitored input 1 is in state "Active 2"
Alternative (step 4 = option 2): Monitored input 1 is in state "Inactive 2"
Alternative (step 4 = option 10): Monitored input 2 is in state "Active 1+2" or
"Inactive 2"
Fast
A system component has an earth fault
Fast
Battery is disconnected or very low charge
Slow
Mains power supply is off (after expiry of the mains delay time) or too low
–
Control input 3 is active (depending on programming, see step15)
–
Fast
–
Monitored input 1 line is on open circuit or short circuit
–
Monitored input 2 line is on open circuit or short circuit
Monitored control line 3 is on open circuit or short circuit
–
Monitored control line 2 is on open circuit or short circuit if step 3, option 22, 23
–
or 24 is selected
Monitored control line 5 is on open circuit or short circuit or fuse blown if step 1,
–
option 18, 19 or 21 is selected
–
During calibration processing of monitored control line 5 if step 1, option 18 or
19 is selected
Lit
Processor fault (the control unit is not operating)
Lit
The unit is in "System test Mode 1" (see chapter 10.7)
Slow
The unit is in "System test Mode 2" (see chapter 10.7)
Lit
–
Monitored control line 1 is disabled
Monitored control line 4 is disabled
–
Monitored control line 2 is disabled if step 3, option 20 or 21 is selected
–
–
Monitored control line 5 is disabled if step 1, option 14, 15, 16 or 21 is selected
Fast
–
Monitored control line 1 is on open circuit or short circuit
Monitored control line 4 is on open circuit or short circuit or fuse blown
–
Monitored control line 2 is on open circuit or short circuit if step 3, option 20 or
–
21 is selected
Monitored control line 5 is on open circuit or short circuit or fuse blown if step 1,
–
option 14, 15, 16 or 20 is selected
–
During calibration processing of monitored control line 4 and 5
Slow
–
Monitored control line 1 is in state "Horn test" (see chapter 10.4)
Monitored control line 1 is in state "Active" in "System test Mode 2" (see
–
chapter 10.7)
Lit
–
Monitored control line 4 is in state "Active" in "System test Mode 1" (see
chapter 10.7)
Calibration processing of monitored control line 4 and 5 is terminated
–
Slow
Monitored control line 4 is in state "Active" in "System test Mode 2" (see chapter
10.7)
Lit
– Driver outputs 1, 2, 8 are disabled (depending on programming, see step 16)
– Monitored control line 2 is disabled if step 3, option 18 or 19 is selected
– Monitored control line 5 is disabled if step 1, option 17 is selected
Fast
–
Monitored control line 2 open circuit or short circuit if step 3, option 18 or 19 is
selected
Monitored control line 5 open circuit or short circuit or fuse blown if step 1,
–
option 17 is selected
During calibration processing of monitored control line 5 if step 1, option 17 is
–
selected
Slow
–
Monitored control line 3 is in state "Warning panel test"
–
Monitored control line 3 is in state "Active" in "System test Mode 2" (see
chapter 10.7)
Lit
Contact 2 is disabled (function may be inoperative)
Alternative (step 13 = option 10):
Automatically activated if access is provided to operating level 2
-
Alternative (step 3 = option 14):
Inoperable, if facility "Remote transmission" not used
Fast
Control input 3 or 4 with option "RT-fault" is "Active" (see step 15)
Lit
–
Monitored control line 5 is in state "Active" in "System test Mode 1" (see
chapter 10.7)
Calibration processing of monitored control line 4 and 5 is terminated
–
Slow
Monitored control line 5 is in state "Active" in "System Test Mode 2" (see chapter
10.7)
Lit
Contact 1 is disabled
–
Monitored control line 2 is disabled if step 3, option 17 is selected
–
Alternative (step 13 = option 10):
Automatically activated if state operating access 2 is provided
-
Alternative (step 3 = option 14 ):
Inoperable, if facility "Remote transmission" facility not used
Fast
Monitored control line 2 is open circuit or short circuit if step 3, option 17 is
selected
Lit
– Monitored input 3 is in state "active 1" (depending on programming, see step 8)
– Control input 2 or 4 is active (depending on programming, see step 15)
Fast
Monitored input 3 is on open circuit or short circuit
Structure and function
27
A6V10099837_a_en
12.2007