First Application - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

Planning
6.2.4

First application

50
Building Technologies
Fire Safety & Security Products
In this application, the functions of the extinguishing control unit are forwarded to
the fire detector control unit, and commands from the fire detector control unit are
transmitted to the extinguishing control unit.
Signals to the fire detector control unit:
Contact 1 reports the state "Released" and if required also "Activated"
Contact 2 reports the state "Fault" as a common fault
Contact 3 reports the state "Fire alarm" and if required also "Activated"
Contacts 4 and 5 report the states "Manual only" and "Autom.& Man. blocked"
Signals from the fire detector control unit:
Control input 1 receives the signal for resetting the extinguishing control unit
Control input 2 receives the signal for blocking Autom. & Manual released
Control input 3 receives the signal for manual only released
Recommended setting of user programming:
Contact 1:
Activated in state "Released" until
"Reset"
Alternative: activated in state "Activated"
and "Released" until "Reset"
Contact 2:
Activated (immediate) in state "Fault"
until the cause is eliminated and "Silence
buzzer"
Contact 3:
Activated in state "Fire alarm" until
"Reset"
Alternative: activated in state "Fire alarm"
and "Activated" until "Reset"
Contact 4:
Activated in state "Manual only"
Contact 5:
Activated in state "Autom. & Man.
blocked"
Control input 1:
RESET inhibited:
- upon "Fire alarm" accepted only after
"Silence buzzer"
- upon "Activated"/"Released" accepted
only after "Silence horn" and running
time of control line 4/5 has elapsed
Control input 2:
To trigger "Autom. & Man. blocked"
Control input 3:
To trigger "Manual only"
Details on programming see chapter 11.6.3, 11.6.9 and 11.6.15.
(step 3 = option 1
PU2 jumper = NO)
(step 3 = option 2
PU2 jumper = NO)
(step 3 = opt. 9 + 10
PU3 jumper = NO)
(step 3 = option 5
PU4 jumper = NO)
(step 3 = option 6
PU4 jumper = NO)
(PU5 jumper = NC)
(PU6 jumper = NO)
(step 9 = option 10)
(step 15 = option 3)
(step 15 = option 14)
A6V10099837_a_en
12.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents