11.6.16 Step 16, change the function of the driver outputs 2, 8 and 1

Change the function of driver output 2
Select
Option
Function
KEY13
1 (default)
Active on "Activated" and "Released"
Active on "Fire alarm" Z1 or Z2 or Z3 if zone 3 is programmed in step
2
11 option 12 or 13
3
Active on "Activated"
Active on normal operation
4
Inactive on "Fault", "Fire alarm" Z1 or 2 or Z3, "Activated", "Released"
Processing as door magnetic
5
Active on "Fault" on control line 5
6
Active in "Normal operation" (microcomputer working)
7
Active on "Mech. blocked"
KEY14
8
Output not "Disable/Enable" with key "Disable/Enable Fire control"
9 (default)
Output "Disable/Enable" with key "Disable/Enable Fire control"
(*) not allowed on state "Activated" and "Released"
Change the function of driver output 8
Select
Option
Function
KEY15
10 (default) Active on "Emergency hold/abort"
11
Active on "Autom. & Man." (normal operation)
12
Active on "Fault power supply"
13
Active on «Loss of agent»
14
Active on "Detector test"
15
Active on "Alarm" zone 3 until "Reset"
16
Active on "Disabled"
17
Active in status isn't "normal operation" (any indication on the XC10)
KEY16
18 (default) Output "Disable/Enable" with key "Disable/Enable Fire control"
19
Output not "Disable/Enable" with key "Disable/Enable Fire control"
(*) not allowed on state "Activated" and "Released"
Change the function of driver output 1
Select
Option
Function
KEY16
20 (default) Output "Disable/Enable" with key "Disable/Enable Fire control"
21
Output not "Disable/Enable" with key "Disable/Enable Fire control"
(*) not allowed on state "Activated" and "Released"
Building Technologies
Fire Safety & Security Products
Programming the user functions
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red Yel. Red Yel.
(*)
Zone 1
Zone 2
Zone 3
Red Yel. Red
Red Yel. Red Yel.
(*)
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel. Red
(*)
A6V10099837_a_en
Zone 4
Zone 4
Yel.
Zone 4
Yel.
89