Programming the user functions

11.6.1 Step 1, changing the activated time and function of control lines 4/5

Change the activated time of control line 4
Select
Option
Function
KEY13
1
Activated time 0 seconds
2
Activated time 5 seconds
3
Activated time 10 seconds
4
Activated time 15 seconds
5
Activated time 20 seconds
6
Activated time 25 seconds
7 (default)
Activated time 30 seconds
8
Activated time 35 seconds
9
Activated time 40 seconds
10
Activated time 45 seconds
11
Activated time 50 seconds
12
Activated time 55 seconds
13
Activated time 60 seconds
Change the function of control line 5
Select
Option
Function
KEY14
Active in state "Activated" but activated time 0 seconds
14 (default)
Processing as "Actuator"
Active same as control line 4
15
Processing as "Actuator"
Active same as control line 1 (horn)
16
Processing as "Horn"
Active in state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is programmed in
17
step 11 options 9, 12 or 13), "Activated" and "Released"
Processing as "Fire Control"
Active in state "Mech. blocked"
18
Processing as " Warning Panel"
Active in state "Auto. & Man. blocked"
19
Processing as "Warning Panel"
Activated in state "Fire alarm" (Z1 or Z2 or Z3 if zone 3 is
20
programmed in step 11 options 9, 10, 12 or 13) and "Activated"
Processing as "Horn"
Active in state "Manual only" or "Autom. & Man. Blocked"
21
Processing as "Warning Panel"
76
Building Technologies
Fire Safety & Security Products
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel.
Lit
Pulsated fast
Pulsated slow
A6V10099837_a_en
Zone 4
Red Yel.
Zone 4
Red Yel.
12.2007