11.6.14 Step 14, Change The Fault Delay Upon "Mains Failure; Step 15, Change The Function Of The Control Inputs 2 To 4 - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

Programming the user functions

11.6.14 Step 14, change the fault delay upon "Mains failure"

Change the fault delay upon "Mains failure"
Select
Option
Function
KEY13
1
Delay = 0 sec
2
Delay = 3 minutes
3 (default)
Delay = 10 minutes
4
Delay = 30 minutes
5
Delay = 3 hours

11.6.15 Step 15, change the function of the control inputs 2 to 4

Change the function of control input 2
Select
Option
Function
KEY13
1 (default)
Initiate function "Silence buzzer"
2
Enable state "Manual only"
3
Enable state "Autom. & Man. blocked"
4
Enable state "External device disabled"
5
Enable "RT-alarm" + "RT-fault" disabled
6
Enable state "Emergency hold"
7
Enable "Control line 1" + "Fire alarm" (LED6)
Change the function of control input 3
Select
Option
Function
KEY14
8 (default)
Enable state "Fault"
9
Enable state "External power supply fault"
10
Enable state "RT-fault"
11
Enable state "Access level 2 enabled"
12
Enable state "Emergency abort"
13
Initiate function "Silence buzzer"
14
Enable state "Manual only"
Change the function of control input 4
Select
Option
Function
KEY15
15 (default) Release "Silence Re-sound Horn" function
16
Enable state "No fault" (inverse)
17
Enable state "RT-fault"
18
Enable state "Access level 2 enabled"
19
Enable state "Emergency abort"
20
Initiate function "Silence buzzer"
21
Enable "Control line 1" & LED6 "Fire alarm"
1
) The state lasts as long as a positive potential is applied to the input
2
) The functions must be triggered by a pulse
3
) As soon as the positive potential is no longer on the input, a fault is
triggered
88
Building Technologies
Fire Safety & Security Products
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel.
Red Yel. Red Yel. Red Yel.
2
)
1
)
1
)
1
)
1
)
1
)
1
)
Zone 1
Zone 2
Zone 3
Red Yel.
Red Yel.
Red Yel. Red Yel.
1
)
1
)
1
)
1
)
1
)
2
)
1
)
Zone 1
Zone 2
Zone 3
Red Yel.
Red Yel. Red Yel.
2
)
3
)
1
)
1
)
1
)
2
)
1
)
A6V10099837_a_en
Zone 4
Zone 4
Zone 4
Zone 4
Red Yel.
12.2007