Programming the user functions
11.6.5 Step 5, change the active mode of control lines 1 and 3
Change the active mode of control line 1
Select
Option
Function
KEY13
1 (default)
State "Fire alarm" = continuous
▼
2
State "Fire alarm" = pulsating slow (1sec active/4sec inactive)
3
State "Fire alarm" = not activated
4
State "Fire alarm" = pulsating fast (1sec active/1sec inactive)
State "Activated" = pulsating fast and pulsating slow in state
5 (default)
"Emergency hold/abort"
6
State "Activated" = continuous
State "Activated" = continuous and pulsating slow in state
7
"Emergency hold"
State "Activated" = pulsating long (4sec active/1sec inactive) and
8
pulsating fast in state "Emergency hold/abort"
KEY14
9 (default)
State "Released" = pulsating fast
▼
10
State "Released" = continuous
Change the active period of control line 1
Select
Option
Function
KEY14
11 (default) Active until "Silence Re-sound horn" and "Reset"
▼
12
Active until "Reset"
Active until "Silence Re-sound horn" and "Reset" but only after timer
13
of 5 min has elapsed
Active until "Silence Re-sound horn" and "Reset" but only after timer
14
of 30 min has elapsed
Change the active mode and active period of control line 3
Select
Option
Function
KEY15
15 (default) State "Fire alarm" = not activated
▼
16
State "Fire alarm" = continuous
17
State "Fire alarm" = pulsating fast
18 (default) State "Activated" = continuous
19
State "Activated" = pulsating fast
KEY16
20 (default) State "Released" = continuous until "Reset"
▼
State "Released" = continuous until "Silence Re-sound horn" or
21
"Reset"
State "Released" = continuous until "Digit key 4" is pressed after
22
"Reset"
23
State "Released" = pulsating fast until "Reset"
State "Released" = pulsating fast until "Silence Re-sound horn" or
24
"Reset"
State "Released" = pulsating fast until "Digit key 4" is pressed after
25
"Reset"
80
Building Technologies
Fire Safety & Security Products
Zone 1
Zone 2
Zone 3
Red Yel. Red
Yel. Red Yel. Red Yel.
–
–
–
Zone 2
Zone 1
Zone 3
Red Yel. Red
Yel.
Red Yel. Red Yel.
–
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red Yel. Red Yel.
–
–
A6V10099837_a_en
Zone 4
Zone 4
Zone 4
–
–
–
–
–
12.2007