11.6.6 Step 6, enable the "Alarm verification" function
Enable "Alarm verification" function of detector zones 1 and 2
Select
Option
Function
KEY13
1 (default)
No alarm verification
▼
Twice line alarm within 60 seconds = Alarm
2
After first line alarm = automatic reset and short flash up of zone LED
Enable "Alarm verification" function of detector zone 3
Select
Option
Function
KEY13
3 (default)
No alarm verification
▼
Twice line alarm within 60 seconds = Alarm
4
After first line alarm = automatic reset and short flash up of zone LED
Enable "Alarm verification" function of detector zone 4
Select
Option
Function
KEY14
5 (default)
No alarm verification
▼
Twice line alarm within 60 seconds = Alarm
6
After first line alarm = automatic reset and short flash up of zone LED
11.6.7 Step 7, define the function of the yellow key (KEY8)
Define the function of the yellow key (KEY8)
Select
Option
Function
KEY13
1 (default)
Deleted
▼
2
Not to be used
3
Not to be used
4
Not to be used
5
Not to be used
6
Not to be used
Change the operating access of the yellow key (KEY8)
Select
Option
Function
KEY14
7 (default)
Deleted
▼
8
Not to be used
KEY15
9 (default)
Deleted
▼
10
Not to be used
Suppress "Reset" upon stopped activated time by the yellow key (KEY8)
Select
Option
Function
KEY16
11 (default) Deleted
▼
12
Not to be used
Building Technologies
Fire Safety & Security Products
Key 8 is not accessible with XC1003-A.
Programming the user functions
Zone 1
Zone 2
Zone 3
Red
Yel. Red Yel. Red Yel. Red Yel.
–
Zone 1
Zone 2
Zone 3
Red
Yel.
Red Yel. Red Yel. Red Yel.
–
Zone 2
Zone 1
Zone 3
Red Yel.
Red
Yel. Red Yel. Red Yel.
–
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red
Yel. Red Yel.
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Zone 3
Zone 1
Zone 2
Red Yel. Red Yel. Red
Yel. Red
–
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel. Red
A6V10099837_a_en
Zone 4
Zone 4
Zone 4
Zone 4
Zone 4
Yel.
–
Zone 4
Yel.
–
81