Power Supply Fcp1004-E - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

5.2.1

Power supply FCP1004-E

Building Technologies
Fire Safety & Security Products
Fig. 7
Components of the power unit FCP1004-E
Ref.
Function
1
Terminal block for setting mains voltage to
115 V
2
Terminal block for mains connection
3
4 AT/250 V 20x50mm high break mains fuse
4
Jumper for system start without mains
power
5
LED green "mains operation" (inside but
visible from the front)
6
Heat sensor for temperature compensation
7
Batteries connection
8
XCM1001-1 connection
9
Connection required in case EN54-2 option
with requirement "Total loss of power" is
mandatory (Mainly for FR).
Connect wire between +battery connection
and +BAT terminal of XCM1001-2
This product shall be installed, commissioned and maintained by trained service personnel in
accordance with the following:
1. IEE regulations for electrical equipment in buildings
2. Codes of practice
3. Any instructions specifically advised by the manufacturer
This equipment is designed to operate from 230V 50Hz mains supplies. It must be connected to a
protective earthing conductor in the fixed wiring of the installation, and a readily accessible double
pole disconnect device meeting the requirements of EN60950/IEC950 which disconnects live and
neutral simultaneously, shall be incorporated in the fixed wiring.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the
protective earth will render the equipment unsafe.
1. Ensure mains power is switched off
2. Remove mains fuse (3)
3. Connect the mains cable to the FCP1004E power supply terminals (2) Protective earth, live and
neutral)
4. Attach the cable with 2 plastic fastenings
This control panel is environmental class A and is designed for indoor use only at temperatures
between -5° C (+/- 3) and +40° C (+/- 2) and with a m aximum relative humidity of 95%.
The IP rating for the enclosure is IP30. Operation outside of these limits may render the equipment
unsafe.
Structure and function
Remarks
Jumper set for 115 V only (use insulated wire)
Remove after system start
Not lit in the event of power failure
Protection by fuse 630 mA
A6V10099837_a_en
19
12.2007