Detailed Procedures; Enabling Access Level 1; Checking All Optical And Acoustic Elements Of The Control Unit; Enabling Access Level 2 - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

10

Detailed procedures

10.1

Enabling access level 1

10.2

Checking all optical and acoustic elements of the control unit

10.3

Enabling access level 2

10.4

Test the alarm horn

10.5

Testing the warning panel

Building Technologies
Fire Safety & Security Products
Normally, operation of the extinguishing control unit is blocked.
Access to level 1 is always possible, only the keys "Silence buzzer" and "Lamp
test" are active.
Check that the optical and acoustic elements of the control unit function correctly.
Proceed as follows:
1. Press the key "Lamp test".
All LEDs light up and the buzzer sounds for approx. 5 seconds.
2. Check whether all LEDs light up and the buzzer sounds.
Normally, operation of the extinguishing control unit is blocked. Operation - Access
level 2 - is enabled using the access code.
In order to enable Access level 2 by using the access code, proceed as follows:
1. Enter the access code "4233" via the numeric keys.
The "Operating access" LED lights up and operation is enabled.
2. To block Access Level 2 again, you must wait. Access level 2 is automatically
blocked again three minutes after the last entry.
The "Operating access" LED is no longer lit.
The alarm horn test relates to monitored control line 1.
Proceed as follows:
1. Set the system on Access level 2.
2. Press and hold down key "Digit 3" and press key "Lamp test".
Control line 1 is active for 30 seconds.
LED 20 flashes slowly for 30 seconds
3. Press key "Silence Re-sound horn" or "Lamp Test" or "Reset".
The alarm horn is silenced before the 30 seconds elapse.
The warning panel test relates to monitored control line 3.
Proceed as follows:
1. Set the system on Access level 2.
2. Press and hold down key "Digit 4" and press key "Lamp test".
Control line 3 is active for 30 seconds.
LED 22 flashes slowly for 30 seconds.
3. Press key "Silence Re-sound horn" or "Lamp test" or "Reset".
The warning panel is turned off before the 30 seconds elapse.

Detailed procedures

65
A6V10099837_a_en
12.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents