11.6.2 Step 2, change the flooding time (active period) of control lines 4/5
Change the flooding time of control line 4
Select
Option
Function
KEY13
1 (default)
Flooding time 30 seconds
▼
2
Flooding time 60 seconds
3
Flooding time 90 seconds
4
Flooding time 120 seconds
5
Flooding time to "Reset"
Change the flooding time of control line 5
Select
Option
Function
KEY14
6 (default)
Flooding time 30 seconds (*)
▼
7
Flooding time 60 seconds (*)
8
Flooding time 90 seconds (*)
9
Flooding time 120 seconds (*)
10
Flooding time to "Reset"
(*) Only relevant if control line 5 is set to option 14 or 15 in
programming step 1. With option 14, control line 5 is already
activated with "Activated" but the selected flooding time starts only
counting with the activation of control line 4.
Building Technologies
Fire Safety & Security Products
Programming the user functions
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red Yel. Red Yel.
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Zone 3
Red Yel. Red Yel.
–
–
–
–
–
–
–
–
A6V10099837_a_en
Zone 4
Zone 4
–
–
–
–
–
–
–
–
77