Programming the user functions

11.6.12 Step 12, change the code for access level 2

Change the basic code for access level 2
Select
Option
Function
KEY13
1 (default)
Access code "4233" defined
Individual access code:
1. Enter the access code by pressing the keys 4 to 7 (digits 1 to 4) in
the desired sequence (max. 4 digits)
2. Press KEY13 (zone 1)
2
3. Repeat steps 1 and 2 (confirm access code)
No access code required (access level 2 is released via key switch)
3
Press key13 & 14 simultaneously after procedure described in option
2 have been done
Change the access level for the function "Silence buzzer"
Select
Option
Function
KEY14
4 (default)
Can always be silenced
5
Possible only on access level 2
86
Building Technologies
Fire Safety & Security Products
LED27 (zone 1, red) flashes
LED27 (zone 1, red) lit continuously (access code accepted)
LED28 (zone 1, yellow) flashes (code not accepted; repeat steps
1 to 3)
Zone 1
Zone 2
Zone 3
Red Yel.
Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel.
Red
Yel. Red Yel. Red Yel.
A6V10099837_a_en
Zone 4
Zone 4
12.2007