6.1.4

Driver outputs

Building Technologies
Fire Safety & Security Products
The signals of driver outputs can be used for relays, for example:
Shutting down the ventilation system
Closing the doors to the extinguishing area
Closing the fire damper
Report status information
Fig. 32
Connection of the driver output to relay
In programming step 16, you can select the following functions:
Driver output 2: Option 1 = Active on state "Activated"/"Released"
Option 2 = Active on state "Fire alarm"
Option 3 = Active on state "Activated"
Option 4 = Active on state "Normal operation", and inactive on
Option 5 = Active on state "Fault control line 5"
Option 6 = Active on state "Normal operation" (µP working)
Option 7 = Active on state "Mech. blocked"
Driver output 8: Option 10 = Active on state "Emergency hold/abort"
Option 11 = Active on state "Autom. & Man." (normal operation)
Option 12 = Active on state "Fault power supply"
Option 13 = Active on state "Loss of extinguishing agent"
Option 14 = Active on state "Detector test"
Option 15 = Active on state "Alarm" zone 3 until "Reset"
Option 16 = Active on state "Disabled"
Option 17 = Active when system is in any condition other than
In the basic configuration, driver outputs are set in programming step 16 as follow:
Driver output 2 is set to be active on state "Activated"/"Released" (= option 1)
and driver output 8 to be active in state "Emergency hold/abort" (= option 10).
Driver outputs 2, 8 and 1 can be disabled with key "Fire control disabled" (=
option 9, 18, 20).
Details on programming, see chapter 11.6.16.
Requirement: Relays must be installed inside the control unit
Note:
Driver outputs 3 to 7 cannot be disabled.
state "Fault"/"Fire alarm"/"Activated"/"Released"
"Normal operation"
Planning
45
A6V10099837_a_en
12.2007