11.6

Programming steps

Select
Step
Function
KEY1
1
Change activated time and function of control lines 4/5
2
Change the flooding time of control lines 4/5
3
Change the function of the remote transmission
4
Change the function of the monitored inputs 1 and 2
5
Change the active mode of control lines 1 and 3
6
Enable the "Alarm verification" function
KEY2
7
Define the function of the yellow key 8
8
Change the function of the monitored Input 3
9
Change the parameters to the "Reset" function
10
Change the indication mode on the operator interface
11
Change of function of detector zones 1 to 3
12
Change the code for Access level 2
13
Change the parameters on the operator interface
14
Change of the fault delay upon "Mains failure"
15
Change of function of control inputs 2 to 4
16
Change of the function of the driver outputs 2, 8 and 1
Building Technologies
Fire Safety & Security Products
1. Access to program mode (see chapter 11.1)
2. Select the desired programming step by pressing KEY1 "Silence Re-sound
Horn" (to work backwards from programming step 16) or KEY2 "Mode select" (to
work forwards from programming step 1)
3. Select the option within the programming step by pressing keys 13 to 16
"ZONES Disable/Enable", "ZONES det. test/Enable", "Silence buzzer", "Reset"
Fig. 46
Operating and indicator elements, XCM1001-2 upper main board view
Programming the user functions
Activated indicator
LED11
Disabled
LED12
Detector test
LED13
Fault
LED14
Loss of agent
LED15
Earth fault
LED16
Power fault
LED17
Peripheral fault
LED18
System fault
LED19
System test
LED20
Horn/actuator
LED21
Disabled/fault
LED22
Fire control
LED23
RT-fault
LED24
Disabled/fault
LED25
RT-alarm
LED26
Emergency hold/abort
A6V10099837_a_en
State
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
lit
75