Step 8, Change The Function Of The Monitored Input 3 - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

Programming the user functions

11.6.8 Step 8, change the function of the monitored input 3

Change the function of the monitored input 3
Select
Option
Function
1 (default)
Function "Emergency abort"
KEY13
In state "Activated":
"Active 1" = ON
"Active 1" cancelled = Abort remains active until reset
In state "Normal":
"Active 1" = ON
"Active 1" cancelled = Abort remains active until reset
2
Function "Emergency hold"
In state "Activated":
"Active 1" = ON
"Active 1" cancelled = Activated time restarts
In state "Normal":
"Active 1" = ON
"Active 1" cancelled = Return to "Normal state"
3
Function "Block"/"Emergency hold" 1
In state "Activated" by detector:
"Active 1" = ON
"Active 1" cancelled = Activated time restarts
"Active 2" = ON
In state "Activated" by manual activation:
"Active 1" = ON
"Active 2" = ON
In state "Normal":
"Active 1" = ON
"Active 1" cancelled = Blocking disabled
"Active 2" = ON
"Active 2" cancelled = Blocking disabled
4
Function "Block"/"Emergency hold" 2
In state "Activated" by detector:
"Active 1" = ON
"Active 1" cancelled = Activated time restarts
In state "Activated" by manual activation:
"Active 1" = ON
In state "Normal":
"Active 1" = ON
"Active 1" cancelled = Blocking disabled
"Active 1" = 680 , "Active 2" = 1k2
82
Building Technologies
Fire Safety & Security Products
= Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
= LED26 lights up
Block the activated process. When new alarm
"
happens, system enters
Fire alarm
= Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
LED26 switches off
Horn turns to "Activated" tone
= LED26 lights up
Block the activated process. When new alarm
happens, system enters "Fire alarm" state
= Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
LED26 switches off
Horn returns to "Activated" tone
= No reaction
= No reaction
= No reaction
= Autom. & Man. blocked
= Manual only
= Activated time is stopped
LED26 lights up
Horn turns to "Hold/Abort" tone
LED26 switches off
Horn returns to "Activated" tone
= No reaction
= Manual only
Zone 1
Zone 2
Red Yel. Red Yel. Red Yel.
"
state
Zone 3
Zone 4
Red Yel.
A6V10099837_a_en
12.2007

Hide quick links:

Advertisement

Table of Contents
loading