Specifications

8.4 Ambient Conditions

Environment
Enclosure size D1h/D2h/D5h/D6h/D7h/D8h
Enclosure type D3h/D4h
Vibration test all enclosure types
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating
- with full output power of typical EFF2 motors (up to 90% output current)
- at full continuous FC output current
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
1) For more information on derating, see section on special conditions in the design guide.
EMC standards, Emission
8
8
EMC standards, Immunity
Energy efficiency class
2) Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.

8.5 Cable Specifications

Cable lengths and cross-sections for control cables
Maximum motor cable length, shielded/armored
Maximum motor cable length, unshielded/unarmored
Maximum cross-section to motor, mains, load sharing, and brake
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
1) For power cables, see electrical tables in chapter 8.1 Electrical Data.
66
®
VLT
AQUA Drive FC 202
S test
2
2)
1)
Danfoss A/S © 11/2016 All rights reserved.
5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
IP21/Type 1, IP54/Type12
IP20/Chassis
Class Kd
Maximum 55 °C (maximum 131 °F)
Maximum 50 °C (maximum 122 °F)
Maximum 45 °C (maximum 113 °F)
0 °C (32 °F)
10 °C (50 °F)
-25 to +65/70 °C (13 to 149/158 °F)
1000 m (3281 ft)
3000 m (9842 ft)
EN 61800-3
EN 61800-3
150 m (492 ft)
300 m (984 ft)
1.5 mm
2
/16 AWG (2x0.75 mm
2
1 mm
/18 AWG
2
0.5 mm
/20 AWG
2
0.25 mm
/23 AWG
MG21A402
1.0 g
1)
1)
1)
IE2
2
)