6.2.3 Ambient Conditions

Environment
Enclosure
Vibration test
Max. THVD
Max. relative humidity
Aggressive environment (IEC 60068-2-43) H
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
6
6
Temperature during storage/transport
Maximum altitude above sea level without derating
EMC standards, Emission
EMC standards, Immunity
1)
See chapter 5.2.1 EMC Test Results

6.2.4 Cable Specifications

Cable lengths and cross-sections for control cables
Max. motor cable length, shielded
Max. motor cable length, non-shielded
Maximum cross-section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross-section to control terminals
1)
For power cables, see electrical tables in chapter 6.1 Electrical Data.
76
Design Guide
IP20/Chassis, IP21/Type 1, IP55/ Type 12, IP66/ Type 4X
5%–93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
Max. 122°F [50°C] (24-hour average maximum 113°F [45°C])
1)
Rev. 2014-04-04 All rights reserved.
1.0 g
10%
class Kd
32°F [0°C]
14°F [10°C]
-13–+149/158°F [-25–+65/70 °C]
3,300 ft [1,000 m]
EN 61800-3, EN 55011
EN61800-3, EN 61000-6-1/2
500 ft [150 m]
1,000 ft [300 m]
2
1.5 mm
/16 AWG
1 mm
2
/18 AWG
2
0.5 mm
/20 AWG
2
0.25 mm
/24 AWG
MG33BF22
1)

Advertisement