2. Commissioning
2.4

Notes on parameters for Idle mode and Fault mode

2−32
Reaction of the outputs in Idle mode or Fault mode
The Idle mode is assumed by the slaves after request by the
master.
The Fault mode defines the status the relevant channel is to
assume in the event of field bus communication faults. The
following applies in this state:
Inputs are transferred
Output channels of the slaves are no longer updated.
In the Idle mode or Fault mode outputs can assume one of
the following states:
Digital outputs/valves
Freeze current status
Reset the output
Set the output
Tab. 2/16: Possible states in the Idle or Fault mode
You can determine the status to be assumed for each output
channel (output or solenoid coil) separately. The standard
setting is Reset output channel".
Further information can be found in the CPX system manual.
Analogue outputs
Freeze current status
Desired analogue value
Festo P.BE−CPX−FB32−EN en 0605NH