Appendix D-Modbus Register Map; C445 Modbus Register Map; Table 128. C445 Modbus Register Map - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Appendix D—Modbus Register Map
Appendix D—Modbus Register Map

C445 Modbus Register Map

Table 128. C445 Modbus Register Map

Register
Name
300
Motor Control Status
301
I Phase A (L1) Scaled
302
I Phase B (L2) Scaled
303
I Phase C (L3) Scaled
304
Avg Current Scaled
305
I Scale Factor
306
Current Unbalance
307
GF Current RMS Scaled
308
Thermal Capacity
309
Time to Trip Overload
310
Remaining Thermal
Capacity
311
Time to Reset Overload
302
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Attribute
Description
BYTE RO
Present Motor Control Status Bits (Running1, Running2, Remote, Tripped,
Warned).
Bitfield
UINT16 RO
Phase A (L1) Motor Current Scaled. Scaled by parameter "I Scale
Factor".
Units: scaled A
UINT16 RO
Phase B (L2) Motor Current Scaled. Scaled by parameter "I Scale
Factor".
Units: scaled A
UINT16 RO
Phase C (L3) Motor Current Scaled. Scaled by parameter "I Scale
Factor".
Units: scaled A
UINT16 RO
Average motor Current Scaled. Scaled by parameter "I Scale Factor".
Units: scaled A
UINT16 RO
This scale factor is applied to all current values monitored via a
communication network.
UINT8 RO
Motor Current Unbalance Percent
Units: %
UINT16 RO
Motor Ground Fault scaled current RMS. Scaled by parameter "I Scale
Factor".
Units: scaled A
UINT8 RO
Thermal Capacity in Percent - An overload trip occurs when the Thermal
Capacity reaches 100%.
Default: 0
Units: %
UINT16 RO
Estimated Time for Overload to Reach Trip Threshold (100% Thermal
Memory)
Units: seconds
UINT8 RO
Thermal Capacity (Percent) Remaining to Trip
Units: %
UINT16 RO
Time for overload to reach reset threshold. The Thermal Memory must
drop below 75% (default value) before a reset is allowed.
Units: seconds
Bit
Description
0
Running 1
1
Running 2
2
Remote enabled
3
Faulted
4
Warning
5
Inhibited
6
Ready
7
Motor at speed
Coil
4785
4786
4787
4788
4789
4790
4791
4792

Advertisement

Table of Contents
loading

Table of Contents