Communication with M-Bus
Byte No.
216
217-222
223
224
225
226
227
228
229
230
231-236
237
238
239
240
241
242
243
244
245-250
251
252
253

10.3.7 Example of the 7th telegram (all values are hexadecimal)

Byte No.
1
2
3
4
5
6
7
8-11
12-13
14
15
16
17
18-19
20
A43/A44
User Manual
Size
Value
1
xx
6
xxxxxxxxxxxx
1
8E
1
C0
1
80
1
40
1
84
1
FF
1
82
1
xx
6
xxxxxxxxxxxx
1
8E
1
C0
1
80
1
40
1
84
1
FF
1
83
1
xx
6
xxxxxxxxxxxx
1
1F
1
xx
1
16
Size
Value
1
68
1
B6
1
B6
1
68
1
08
1
xx
1
72
4
xxxxxxxx
2
4204
1
02
1
02
1
xx
1
xx
2
0000
1
8E
220
Description
VIFE status
Apparent exported energy, L1
DIF size, 12 digit BCD
DIFE, Unit bit 0
DIFE, Unit bit 1
DIFE, Unit bit 2, unit bit0-2-> unit 5
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L2
VIFE status
Apparent exported energy, L2
DIF size, 12 digit BCD
DIFE, Unit bit 0
DIFE, Unit bit 1
DIFE, Unit bit 2, unit bit0-2-> unit 5
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L3
VIFE status
Apparent exported energy, L3
DIF, more records will follow in next telegram
CS checksum, calculated from C field to last data
Stop character
Description
Start character
L-field, calculated from C field to last user data
L-field, repeated
Start character
C-field, RSP_UD
A-field, address
CI-field, variable data respond, LSB first
Identification Number, 8 BCD digits
Manufacturer: ABB
Version
Medium, 02 = Electricity
Number of accesses
Status
Signature (0000 = no encryption)
DIF size, 12 digit BCD
2CMC48001M0201
Revision: C