Communication with M-Bus
10.5.10
Reset of stored state for input 1
Reset of stored state for input 1 is performed by sending the following command
(all values are hexadecimal). The command is not affected by the write protection
level set.
Byte No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
10.5.11
Reset of stored state for input 2
Reset of stored state for input 2 is performed by sending the following command
(all values are hexadecimal). The command is not affected by the write protection
level set.
Byte No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2CMC48001M0201
Revision: C
Size
Value
Description
1
68
Start character
1
08
L-field, calculated from C field to last user data
1
08
L-field, repeated
1
68
Start character
1
53/73
C-field, SND_UD
1
xx
A-field, address
1
51
CI-field, data send, LSB first
1
C0
DIF size, no data, storage number 1
1
40
DIFE unit=1
1
FD
VIF extension of VIF codes
1
9B
VIFE digital input
1
07
VIFE clear
1
xx
CS checksum, calculated from C field to last data
1
16
Stop character
Size
Value
Description
1
68
Start character
1
09
L-field, calculated from C field to last user data
1
09
L-field, repeated
1
68
Start character
1
53/73
C-field, SND_UD
1
xx
A-field, address
1
51
CI-field, data send, LSB first
1
C0
DIF size, no data, storage number 1
1
80
DIFE unit=0
1
40
DIFE unit=2
1
FD
VIF extension of VIF codes
1
9B
VIFE digital input
1
07
VIFE clear
1
xx
CS checksum, calculated from C field to last data
1
16
Stop character
279
A43/A44
User Manual