Communication with M-Bus

10.4.3.1 Examples of Readouts of Previous Values

Readout of previous values data
Sending initialize
command 10 40 fe 3e 16
Reading
acknowledge e5
System sends read request command for demand with date 11-01-08
68 0a 0a 68 73 fe 51 02 ec ff f9 19 68 11 3a 16 ; Date 8th January, year
11 Reading acknowledge
e5
System sending Request User Data 2:
10 7b fe 79 16
Meter sends out data telegram 1:
68 e3 e3 68 08 00 72 00 00 00 00 42 04 10 02 01 2a 00 00; Data header
ce 00 ed eb 00 00 00 00 08 01 11; Date/Time stamp for previous values, here
08-01-11 / 00:00:00 (day-month-year / sec:min:hour)
ce 00 84 00 39 58 17 00 00 00; Daily value for total import active energy,
here 1758.39 kwh
ce 40 84 00 35 18 27 01 00 00; Daily value for total export active energy,
here 12718.35 kwh
ce 80 40 84 00 23 75 02 00 00 00; Daily value for total import reactive
energy, here 275.23 kvarh
ce c0 40 84 00 35 02 00 00 00 00; Daily value for total export reactive
energy, here 2.35 kvarh
ce 00 84 ff 81 00 27 83 75 07 00 00; Daily value for active energy import L1,
here 77583.27 kwh
ce 00 84 ff 82 00 23 75 02 00 00 00; Daily value for active energy import L2,
here 275.23 kwh
ce 00 84 ff 83 00 35 02 00 00 00 00; Daily value for active energy import L3,
here 2.35 kwh
ce 40 84 ff 81 00 39 58 17 00 00 00; Daily value for active energy export L1,
here 1758.39 kwh
ce 40 84 ff 82 00 35 18 27 01 00 00; Daily value for active energy export L2,
here 12718.35 kwh
ce 40 84 ff 83 00 27 83 75 07 00 00; Daily value for active energy export L3,
here 77583.27 kwh
A43/A44
User Manual
246
2CMC48001M0201
Revision: C