Reset Resettable Reactive Energy Import; Reset Resettable Reactive Energy Export - ABB A43 User Manual

Hide thumbs Also See for A43:
Table of Contents

Advertisement

Communication with M-Bus
Byte No.
15
10.5.30

Reset resettable reactive energy import

Reset of resettable active energy export is performed by sending the following
command (all values are hexadecimal). The command is affected by the write
protection level set.
Byte No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
10.5.31

Reset resettable reactive energy export

Reset of resettable active energy export is performed by sending the following
command (all values are hexadecimal). The command is affected by the write
protection level set.
Byte No.
1
2
3
4
5
6
7
8
9
10
11
12
2CMC48001M0201
Revision: C
Size
Value
Description
1
16
Stop character
Size
Value
Description
1
68
Start character
1
08
L-field, calculated from C field to last user data
1
08
L-field, repeated
1
68
Start character
1
53/73
C-field, SND_UD
1
xx
A-field, address
1
51
CI-field, data send, LSB first
1
80
DIF size, no data
1
80
DIFE, unit=0
1
40
DIFE unit=2
1
84
VIFE specifying energy
1
FF
VIFE next byte is manufacturer specific
1
F2
Resettable registers
1
07
VIFE clear
1
xx
CS checksum, calculated from C field to last data
1
16
Stop character
Size
Value
Description
1
68
Start character
1
0A
L-field, calculated from C field to last user data
1
0A
L-field, repeated
1
68
Start character
1
53/73
C-field, SND_UD
1
xx
A-field, address
1
51
CI-field, data send, LSB first
1
80
DIF size, no data
1
C0
DIFE, unit=1
1
40
DIFE unit=3
1
84
VIFE specifying energy
1
FF
VIFE next byte is manufacturer specific
289
A43/A44
User Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A44

Table of Contents