ABB A43 User Manual page 218

Hide thumbs Also See for A43:
Table of Contents

Advertisement

Communication with M-Bus
Byte No.
Size
Value
84
1
83
85
1
xx
86-91
6
xxxxxxxxxxxx
92
1
8E
93
1
80
94
1
80
95
1
40
96
1
84
97
1
FF
98
1
81
99
1
xx
100-105
6
xxxxxxxxxxxx
106
1
8E
107
1
80
108
1
80
109
1
40
110
1
84
111
1
FF
112
1
82
113
1
xx
114-119
6
xxxxxxxxxxxx
120
1
8E
121
1
80
122
1
80
123
1
40
124
1
84
125
1
FF
126
1
83
127
1
xx
128-133
6
xxxxxxxxxxxx
134
1
8E
135
1
40
136
1
84
137
1
FF
138
1
81
139
1
xx
140-145
6
xxxxxxxxxxxx
146
1
8E
147
1
40
148
1
84
149
1
FF
A43/A44
User Manual
Description
VIFE L3
VIFE status
Reactive imported energy, L3
DIF size, 12 digit BCD
DIFE
DIFE
DIFE, Unit 4
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L1
VIFE status
Apparent imported energy, L1
DIF size, 12 digit BCD
DIFE
DIFE
DIFE, Unit 4
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L2
VIFE status
Apparent imported energy, L2
DIF size, 12 digit BCD
DIFE
DIFE
DIFE, Unit 4
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L3
VIFE status
Apparent imported energy, L3
DIF size, 12 digit BCD
DIFE, Unit 1
VIF for units kWh with resolution 0,01kWh
VIFE next byte is manufacturer specific
VIFE L1
VIFE status
Active exported energy, L1
DIF size, 12 digit BCD
DIFE, Unit 1
VIF for units kWh with resolution 0,01kWh
VIFE next byte is manufacturer specific
218