Communication with M-Bus

10.5.6 Set voltage transformer (VT) ratio - primary voltage

The voltage transformer ratio (VT) primary voltage is set by sending the follow-
ing command (all values are hexadecimal). The command is affected by the write
protection level set.
Byte No.
1
2
3
4
5
6
7
8
9
10
11-14
15
16

10.5.7 Set current transformer (CT) ratio - secondary current

The current transformer ratio (CT) secondary current is set by sending the follow-
ing command (all values are hexadecimal). The command is affected by the write
protection level set.
Byte No.
1
2
3
4
5
6
7
8
9
10
11-14
15
16
2CMC48001M0201
Revision: C
Size
Value
Description
1
68
Start character
1
0a
L-field, calculated from C field to last user data
1
0a
L-field, repeated
1
68
Start character
1
53/73
C-field, SND_UD
1
xx
A-field, address
1
51
CI-field, data send, LSB first
1
04
DIF size, 32 bit integer
1
FF
VIF next byte is manufacturer specific
1
21
VIFE VT ratio primary voltage
4
xxxxxxxx
New VT ratio primary voltage
1
xx
CS checksum, calculated from C field to last data
1
16
Stop character
Size
Value
Description
1
68
Start character
1
0a
L-field, calculated from C field to last user data
1
0a
L-field, repeated
1
68
Start character
1
53/73
C-field, SND_UD
1
xx
A-field, address
1
51
CI-field, data send, LSB first
1
04
DIF size, 32 bit integer
1
FF
VIF next byte is manufacturer specific
1
22
VIFE CT ratio secondary current
4
xxxxxxxx
New CT ratio secondary current
1
xx
CS checksum, calculated from C field to last data
1
16
Stop character
277
A43/A44
User Manual