ABB A43 User Manual page 248

Hide thumbs Also See for A43:
Table of Contents

Advertisement

Communication with M-Bus
Readout of previous values data
System sends read request command for previous values with date 1:st of july 06:
68 0A 0A 68 73 FE 51 02 EC FF F9 19 C1 07 89 16
Meter sends out acknowledge:
E5
System sends out request UD2:
10 7B FE 79 16
Meter sends out data telegram:
68 85 85 68 08 00 72 44 47 24 00 42 04 02 02 09 00 00 00
The date/time stamp and the monthly values have storage number 1, that is, it
is the 1:st (most recent in time) set of monthly values read out
CE 00 ED 6B 00 00 00 01 07 06
01-07-06 / 00:00:00 (day-month-year / sec:min:hour)
CE 00 04 35 08 00 00 00 00
10 04 62 02 00 00 00 00
04 27 02 00 00 00 00
79 00 00 00 00 00
CE 80 10 04 65 02 00 00 00 00
2.65 kWh
CE 80 40 04 04 02 00 00 00 00
2.04 kvarh
CE 90 40 04 64 00 00 00 00 00
0.64 kWh
CE B0 40 04 19 00 00 00 00 00
0.19 kWh
CE 80 50 04 65 00 00 00 00 00
0.65 kWh
CE 40 FD 61 00 00 00 00 00 00
CE 80 40 FD 61 00 00 00 00 00 00
1F
62 16
System sends out request UD2:
10 5B FE 59 16
Meter sends out data telegram:
A43/A44
User Manual
;Monthly value for tariff 1 active energy, 2.62 kWh
;Monthly value for tariff 2 active energy, 2.27 kWh
;Monthly value for tariff 3 active energy, 0.79 kWh
;Dif 1F -> more monthly values exist
;Checksum and stop byte
248
;Date/time stamp for previous values, here
;Monthly value for total active energy, 8.35 kWh
;Monthly value for tariff 4 active energy,
;Monthly value for total reactive energy,
;Monthly value for tariff 1 reactive energy,
;Monthly value for tariff 3 reactive energy,
;Monthly value for tariff 4 reactive energy,
;Monthly value for input 1 counter, 0 pulses
;Monthly value for input 2 counter, 0 pulses
;Data header
CE
CE 20
CE 30 04
2CMC48001M0201
Revision: C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A44

Table of Contents