Communication with Modbus
Step
4
5
6
Turn off a
Follow the steps in the table below to turn off a pulse output instance:
pulse output
Step
1
2
Read pulse
Follow the steps in the table below to read the current pulse output configuration:
output
Step
configuration
1
2
3
4
5
6

9.10.6 Tariffs

Tariff configuration defines the currently used tariff source, i.e. communication,
General
clock or inputs. It also defines the settings that are specific for each of these
sources.
Mapping table
The following table shows an overview of the mapping table:
Quantity

Tariffs

Tariffs
Tariffs
A43/A44
User Manual
Action
Write the desired pulse frequency to the Pulse frequency active or reactive
energy registers, depending on the chosen energy type.
Write the desired pulse length to the Pulse length registers.
Repeat steps 1 to 5 for all pulse outputs.
Action
Choose the pulse output instance to configure by writing a number to the Pulse
output instance register. Allowed values are 1-4.
Write the value 1 to the Turn off pulse output register.
Action
Choose the pulse output instance to read configuration for by writing a number
to the Pulse output instance register. Allowed values are 1-4.
Read the Port number register to get the I/O port number used by the chosen
pulse output instance.
Read the Energy quantity registers to get the OBIS code of the quantity used
for the chosen pulse output instance.
Read the Pulse frequency active or reactive energy registers, depending on the
chosen energy type, to get the pulse frequency used by the chosen pulse
output instance.
Read the Pulse length registers to get the pulse length used by the chosen
pulse output instance.
Repeat steps 1 to 5 for all pulse outputs.
Details
Tariff source
Input configuration
Season configuration
156
Start Reg (Hex)
Size
8C90
1
8C91
1
8C92
35
2CMC48001M0201
Revision: C